Measuring heads
| Measuring head | gas | Measuring range |
| Pellistor Sensor (Heat Transducer) | ||
| Pellistor Sensor | Methane, Propane, Butane | 0–100% LEL |
The GM Ecoline HC 50 is a gas detector for natural gas/methane (CH₄) and LPG/liquefied petroleum gas (propane C₃H₈ | butane C₄H₁₀).
The “Ecoline” system from Bieler+Lang was developed for private and public buildings in accordance with DVGW requirements.
It responds even to low concentrations of flammable gases such as natural gas or liquefied petroleum gas. In the event of an alarm, the built-in buzzer sounds, and the connected safety valves or other safety measures are activated.
This provides active protection that safeguards people in public buildings, but also lets you and your family sleep soundly in your own home.
The GM Ecoline HC 50 was developed specifically for the Ecoline series by Bieler+Lang and is used in countless boiler rooms, building service rooms, gas transfer rooms, and gas meter rooms, as well as near gas water heaters and in kitchens.
The GM Ecoline HC 50 has proven itself in the private, public, and commercial sectors for decades.
Conclusion: Standalone gas monitoring in buildings. Ecoline is streamlined to the essentials—for simple and reliable gas monitoring.
| Measuring head | gas | Measuring range |
| Pellistor Sensor (Heat Transducer) | ||
| Pellistor Sensor | Methane, Propane, Butane | 0–100% LEL |
The GM Ecoline HC 50 can be used to monitor the following gases:
The Bieler+Lang Ecoline system is a compact gas detection system for private and public buildings. With up to 4 gas detectors, Ecoline reliably monitors natural gas/methane (CH₄) and LPG/liquefied petroleum gas (propane C₃H₈ | butane C₄H₁₀) in boiler rooms, building service connections, gas transfer rooms, and gas meter rooms.
Ecoline can be used, for example, in schools, youth centers, senior living facilities, kindergartens, gymnasiums, and event halls, as well as in many other public buildings. Our Ecoline has also proven itself over the years in countless private homes and many smaller commercial buildings. The Ecoline can be connected to the building management system via relay contacts, but its actual protective function operates independently.
The other advantages are obvious: Ecoline responds even to low concentrations of flammable gases. Up to 4 GM Ecoline HC 50 gas detectors can be operated with the compact GMC Ecoline 8304 control unit. This allows for the monitoring of up to four hazard zones for gas leaks. In the event of an alarm, the GMC Ecoline 8304 control unit activates the technical safety measures via relay outputs and closes a connected solenoid valve in the gas supply line. An integrated buzzer provides an audible alarm.
This gas detection system complies with the European standard for protection against gas leaks in public buildings, such as schools, nursing homes, and daycare centers, as well as in private residences and small commercial buildings. The system is designed for the reliable detection of natural gas and liquefied petroleum gas (LPG/butane). Up to four hazard zones can be monitored.
The design of this gas detection system is based on DVGW (German Technical and Scientific Association for Gas and Water) Worksheet G110. Its key requirement regarding the use of a gas detection system is that it must be tested by a notified body in accordance with DIN EN 50194.
Digital Security: The Ecoline monitors and protects completely autonomously—that is, independently of networks, Internet connections, or building management systems. This reduces the risk of digital attacks and enables reliable gas monitoring even without a network connection. At the same time, the Ecoline can be integrated into the building management system. However, its actual protective function operates autonomously.
| Part number | 12.600739.3 |
|---|---|
| Sensor type | Heat tinting (catalytic combustion) |
| Measuring range | 0 – 100 % LEL |
| Approvals | Tested according to DIN EN 50194 |
| Detectable gases | Methane, propane, butane |
| Measuring signal | linear 4 -20 mA |
| One-person calibration | with multimeter and test gas |
| Enclosure protection class | IP 44 |
| Further information | See data sheet |