ExDetector SC 220

The ExDetector SC 220 can be used to detect flammable gases and vapors in the measuring range from 0 to 50 % LEL. A semiconductor gas sensor is used for measurement, which is very robust. This is often a sensible alternative to other sensors that cannot be used due to the presence of catalyst poisons in the atmosphere.

The ExDetector SC 220 is stand-alone capable, i.e. it can independently initiate protective measures without the additional use of an evaluation unit. Integrated low-voltage switching outputs for pre-alarm, main alarm and sensor fault are available. It can also be conventionally connected to an evaluation unit.

The ExDetector SC 220 can be used in Ex zone 2.

 

Special features:
  • Explosive gases and vapors
    Sensor type M: Methane, …
    Sensor type P: Propane, heptane, hydrogen, …
    Sensor type S1: Frigene such as R134a, …
  • Measuring range 0 – 50 % LEL (lower explosion limit)
  • Measuring principle Semiconductor gas sensor
  • Stand alone mode possible
  • One-person calibration with Calibrationbox-i

 

Our quality standards:
  • Solid design in a robust housing
  • Durable with low maintenance costs
  • Developed and manufactured in Germany
Send request
Name

By clicking Submit, I confirm that I have read and agree to the privacy policy.

Measuring heads

Part No. Gases Measuring range
ExDetector SC 220 M
12.600758.4 Type M, gas group: methane, hydrogen,… Measuring range 0-50 %LEL
ExDetector SC 220 P
12.600755.4 Type P, gas group: propane, heptane,… Measuring range 0-50 %LEL
ExDetector SC 220 S1
12.600759.6 Type S1 Gas group: Refrigerant/frigene e.g. R134a Measuring range 0-50 %LEL

Measurable gases

The following gases can be monitored with the ExDetector SC 220.

  • Flammable gases
  • Flammable vapors
  • Methane
  • Hydrogen
  • Propane
  • Heptane
  • R134a
  • ….

Description

The ExDetector SC 220 can be used to detect flammable gases and vapors in the measuring range from 0 to 50 % LEL. A semiconductor gas sensor is used for measurement, which is very robust. It is often a sensible alternative to other sensors that cannot be used due to the presence of catalyst poisons in the atmosphere.

 

The ExDetector SC 220 can be used in Ex zone 2.

Because safety counts.

The ExDetector SC 220 is stand-alone capable, i.e. it can independently initiate protective measures without the additional use of an evaluation unit. Integrated low-voltage switching outputs for pre-alarm, main alarm and sensor fault are available. It can also be conventionally connected to an evaluation unit.

Standalone mode
The integrated alarm evaluation is switched on. Two alarm levels with switch-off hysteresis can be stored in the programming. Alarm level 1 (pre-alarm) switches a non-latching NC contact and alarm level 2 (main alarm) switches a latching NC contact. After falling below this alarm threshold, the alarm is retained and must be acknowledged via the reset input. A fault signaling contact signals malfunction and overrange. In addition, the measured value is output as a 4 – 20 mA current signal for further processing.

Transmitter CL
If the alarm evaluation functionality is not required, the sensor can be operated with the integrated CL option. In this case, the sensor supplies the measured gas concentration in the form of a 4 – 20 mA current signal for
further processing in an alarm control center; the alarm switching contacts are not activated. Suitable signal conditioning instruments include GMC 8043, GMC 8032, GMC 8022, GMC 8022E, GMC 8364.

Features of the ExDetector SC 220:

  • Explosive gases and vapors – 3 sensor types available:
    Sensor type M: Methane, …
    Sensor type P: Propane, heptane, hydrogen, …
    Sensor type S1: Frigene such as R134a, …
  • Measuring range 0 – 50 % LEL (lower explosion limit)
  • Measuring principle Semiconductor gas sensor
  • Stand alone mode possible
  • One-person calibration with Calibrationbox-i
  • Linear measuring signal 4 – 20 mA
  • Integrated switching outputs for:
    – Alarm 1 (pre-alarm)
    – Alarm 2 (main alarm)
    – Sensor fault

 

Accessories

  • Test gas set
  • Calibration gases
  • Calibrationbox-i control unit
  • Evaluation devices
  • Mounting bracket
  • Remote gassing adapter FBA2018

Technical Data

Sensor type

Semiconductor gas sensor

Measurable gases

Flammable gases and vapors:
Sensor type M: Methane, hydrogen
Sensor type P: Propane, heptane
Sensor type S1: R134a

Measuring signal

linear 4 -20 mA

Field of application

Ex area zone 2

ATEX marking

II 3 (2) G
Ex nA de [ib] IIC T4 Gc
PTB 07 ATEX 1002

One-man calibration

Calibrationbox-i control unit

Further information

See data sheet

Downloads

Accessories

Verwandte Produkte