GMC 8022 E

The GMC 8022 E evaluation unit is a gas measuring computer for 19″ slide-in housings.

In conjunction with up to 2 sensors with 4 to 20 mA signal output, the GMC 8022 E is used to display and trigger protective measures.

The GMC 8022 E has a measurement function certificate BVS 03 ATEX G007 X.

It is suitable for use in functional safety areas in accordance with SIL 1 and SIL 2.

Special features:
  • SIL 1 + SIL 2
  • Measurement function report BVS 03 ATEX G007 X
  • Simple operation
Our quality standards:
  • Solid and proven device design
  • Very durable with low maintenance costs
  • Developed and manufactured in Germany

 

 

Send request
Name

By clicking Submit, I confirm that I have read and agree to the privacy policy.

Description

The GMC 8022 E evaluation unit is a gas measuring computer for 19″ slide-in housings.

The GMC 8022 E has the following functions in conjunction with sensors with 4-20 mA signal output:
● Measurement and display of the gas concentration.
● Monitoring and warning of these gases.
● Triggering of protective measures to counteract an increase in concentration.
● Horns, warning lights or solenoid valves can be activated, for example, to initiate appropriate measures in the event of gas leakage.

The GMC 8022 E has a measurement function certificate BVS 03 ATEX G007 X.

It is suitable for use in areas of functional safety in accordance with SIL1 + SIL2.

Checking the alarm output is also possible with the GMC 8022 E without test gas.

● Fault monitoring at
– Power failure
– Computer fault
– Wire breakage / short circuit of the sensor lines
● Floating relay outputs for
– Alarm 1 and 2
– Horn
– Fault
● Analog output (only with GMC 8022E)

Key features of the GMC 8022 E:
  • SIL1 + SIL 2
  • Measurement function report available
  • Up to 2 gas sensors
  • 4 to 20 mA
  • for 19″ slide-in module 12TE/3 U
  • 2 alarm levels
  • Additional horn output

 

Available accessories:
  • Central emergency power supply
  • Also for GMC 8022 E:
    – Power supply units
    – 4-20 mA output modules
    – Relay cards RK1, RK2 for switching mains voltage up to 2A
  • Horns
  • Warning lights
  • Solenoid valves

Technical Data

Measuring channels

2

EU type examination

in accordance with Directive 2014/34/EU, measuring function: BVS 03 ATEX G 007 X

Functional safety

SIL 1, SIL 2
(see separate information for details)

Sensor interface

Linear input 4…20 mA,
Shunt 226 Ohm to GND
Sensor supply: 24VDC (20…27.6 VDC), SELV,
max. 100 mA per sensor
PTB 00 ATEX 1075

Alarm levels

Selectable alarm output:
● Individual alarm
– Alarm 1 of each sensor
– Alarm 2 of each sensor
– Horn sensor 1 and 2
– Fault sensor 1 and 2

Outputs

● Individual alarm relay with potential-free contact:
– Alarm 1: NC contact
– Alarm 2: NC contact
● Collective alarm relay with potential-free contact:
– Fault: NC contact
– Horn: NC contact

Switching capacity of the output relays

50 VAC, 1A
75 VDC, 1A

Supply voltage

– 230 VAC, 50…60 Hz
– 24 VDC (21.7…28 VDC,) SELV
for connection to standard
AC/DC power inverters

Display elements

● LEDs for each measuring channel for:
– Alarm 1 and 2
– Fault
– Displayed sensor
● Ready for operation
● Horn
● Digital display for gas concentration and
Programming data

Control elements

3 buttons for:
● Horn and alarm reset
● Guidance through menus
● Programming

Further information

See data sheet