The ExDetector HC 150 is used to measure the current concentration of explosive gases and vapors.

The ExDetector HC 150 can be used to detect explosive gases and vapors in the measuring range from 0 to 100 % LEL. The measuring principle is based on catalytic combustion (pellistor). This measuring principle can be used to monitor a large number of gases, e.g. hydrogen and hydrocarbons.

It additionally meets all criteria for use in Ex zone 2 and in areas of functional safety according to SIL-1.

Variant: ExDetector HC 150 K

The ExDetector HC 150-K sensor was specially developed for duct installation.

Technical data:

  • Application area EX area Zone2:
      II 3G
      Ex nA de IIC T4 Gc
      PTB 10 ATEX 1023
  • Measurement function (conformity statement): BAM 16 ATEX 0801 X
  • detectable gases:
    explosive gases and vapors
  • Measuring range 0 – 100 % LEL (lower explosion limit)

  • Measuring principle catalytic combustion (pellistor)
  • linear measuring signal 4 – 20 mA
  • One-man calibration – direct calibration at the detector
  • 3-wire technology

Datasheet

Datasheet ExDetector HC 150

Controller

Bieler+Lang GMC 750

GMC 750 / GMC 650 / GMC 635

The GMC 750, the flagship of the BUS series, is a truly user-friendly evaluation system with a touchscreen for controlling detectors and devices.
The GMC 750 can manage up to 350 devices and 128 detectors, is fully digital, and can be connected via WiFi.

GMC 8022

The GMC 8022 is a gas measuring computer for up to 2 measuring points. It is designed for mounting on top-hat rails.

Measuring function:
BVS 03 ATEX G 007 X

GMC 8022 E

The GMC 8022 E is a gas measuring computer for mounting in a 19″ rack housing.

Measuring function:
BVS 03 ATEX G 007 X

Service

Safety must be maintained

Service

Maintenance &

Maintenance contracts