Smart-P1
Detector
Gasmonitor Smart-P1
Single gas sensor for underground garages, available in CO or NO2 versions; with RS485 serial output.
Technical data
- For use in conjunction with the type
GMC Multiscan ++PK 265/128/64/32 - for the detection of toxic gases in underground garages
- Carbon monoxide CO: 0 -300 ppm
Nitrogen dioxide NO2: 0-30 ppm - Electrochemical cell for CO and NO2
- 12-24 Volt DC (-20% +15%)
- CO max. 70 mA
NO2 max. 70mA - Serial RS485
- 5% FS
- -25 to +60 °C
- 20 – 90% non-condensing RH/40 °C
- IP55
- aluminum housing (100x180x65 mm), 600 g
- CO sensor approx. 4 years
- NO2 sensor approx. 3 years
- DIN EN 50545-1 (TÜV Rheinland)
- direct calibration at the sensor
Data sheet
Data sheet Gasmonitor Smart-P1
Evaluators
Multiscan++ Park
The GMC Multiscan ++ Park is a gas detection panel designed in accordance with the EN 50545-1 standard for monitoring toxic gases in underground garages.