Multiscan ++Park

Controller

Multiscan ++Park

The GMC Multiscan ++ Park is a gas detection panel designed in accordance with the EN 50545-1 standard for monitoring toxic gases in underground garages.

The control panel can manage and monitor up to 256 gas detectors. These can be bus sensors in loops or analog 4-20 mA sensors connected via separate 8-input cards STG/IN 8 PK.

Three alarm thresholds can be set for each connected gas detector. Averaging is possible from 5-60 minutes for alarm threshold 1 and 2, between 1 and 5 minutes for alarm threshold 3.

The control panels already include 8 relays onboard. The system architecture allows the extension of the outputs up to 256 by separate 16-output cards STG/OUT 16-S.

Technical data

  • Sheet steel housing IP 65 (L:470, H:426, D:148 mm) or 19″ 3U Rack
  • Maximum 256 probes when connecting both RS 485 loops and 4-20mA via STG/IN8-PK modules
  • 8 relays onboard plus 64 (128,256 or 512) open collector outputs with STG/OUT16-S modules
    (Optional STG/8REL relay cards)
  • 2 x RS485 (2 for PK32) , 1 x RS 232 interfaces
  • 110-230V AC 50/60Hz in sheet steel housing
  • 24 V DC in 19″ rack version
  • max. 10 VA power consumption

  • Graphic LCD slide display
  • 2x 9 LED indicators
  • 0-55°C Operating temperature
  • 15-85% rel. humidity

Datasheet

Datasheet Mulitscan ++Park

Detector

Gasmonitor Smart-P1

Single gas sensor for underground garages, available in CO or NO2 versions; with RS485 serial output.

Service

Safety must be maintained

Service

Maintenance &

Maintenance contracts